Simex
INDICATORS – CONTROLLER SIMEX
Simex Multicon CMC-99 is a compact multichannel controller with the ability to archive all data. One of the few controllers with built-in advanced features (PID, ON / OFF, time & profiles)
Simex MultiCon
Simex SRP – 73
POWER SUPPLY
19V ÷ 50V DC; 16V ÷ 35V AC or 85 ÷ 260V AC / DC
INPUTS
current 0-20 mA or 4-20 mA, programmable, input resistance 50 kOhm; millivoltage 0-60 mV, 0-75 mV, 0-100 mV, 0-150 mV; programmable; Input resistance> 100 kOhm
DISPLAY
LED, two-colored (red-green), 4 x 13 mm (IP 40) – standard or LED, red, 5 x 9 mm (IP 65) – option
SPAN
-999 ÷ 9999 + decimal point
CONSUMPTION
85 ÷ 260V AC / DC and 16V ÷ 35V AC power supply: max. 4,5 VA; 19V ÷ 50V DC power supply: max. 4,5 W
OUTPUTS
0, 1 or 2 relays 1A / 250V AC (cos fi = 1) or OC 30mA / 30VDC / 100mW; transducer power supply output: 24V DC + 5%, -10% / max. 100 mA, stabilized, not insulated from measuring inputs
COMMUNICATION
RS-485, 8N1 and 8N2, 1200 bit / s ÷ 115200 bit / s, Modbus RTU (not galvanically isolated from measuring inputs)
ACCURACY
± 0.25% ± one digit in the entire operation range
TRS – Temperature and humidity measurement system
- Measurement, recording and storage of temperature and humidity data
- Up to 127 measuring points can be connected
- Two types of user interface (basic and andvanced)
- GSM / GPRS
- Advanced alarm functions
- Easy installation and application
SLIK-94 – COUNTER (DOSER)
POWER SUPPLY
19V ÷ 50V DC; 16V ÷ 35V AC or 85 ÷ 260V AC / DC
INPUTS
pulse, 2 x counting; 1 x programmable, 1 x reset
OPERATIONS
addition, subtraction and square
DISPLAY
LED, red (green on request), 6 x 13 mm
DATA MEMORY
non-volatile memory, EEPROM type
SPAN
-99999 ÷ 999999
CONSUMPTION
85 ÷ 260V AC / DC and 16V ÷ 35V AC power supply: max. 4,5 VA; 19V ÷ 50V DC power
supply: max. 4,5 W
OUTPUTS
0, 2 or 4; relay 1A / 250V AC (cosφ = 1) or OC 30mA / 30VDC / 100mW; power supply output:
24V DC + 5%, -10% / max. 100 Ma
COMMUNICATION
RS-485, 1200 ÷ 115200 bit / s, 8N1 and 8N2, Modbus RTU
RESET
reset: button and electric, with keylock
View the full SIMEX program